Telecommunications
Providing innovative and comprehensive solutions for Telecom power and cooling since 1995.Polar Power provides prime power and backup solutions that are:
Polar Power meets the customers’ program goals for increased reliability, reduced maintenance, and fuel efficiency though our many years of experience and our willingness to invest in new tooling and technology.
Polar DC Hybrid Power Solution Combining Renewable Energy and Fuel Polar Power’s Hybrid solution consists of a DC generator which charges the battery and powers the load at the same time. The DC generator is designed to shut down after the battery is charged and the load demand is low. The battery provides power to the load while the generator is shut down. This is an energy efficient alternative to an AC generator operating 24/7. Polar Power’s hybrid power solution allows the convenient integration of solar and wind for fuel reduction and lower generator maintenance. Solar and wind can be added at any time and incrementally.
HYBRID POWER SYSTEM 24/48 VDCFor most Telecom applications the use of 100% solar and wind power is not practical. This is due to high CAPEX cost, lower reliability, higher maintenance, and significantly more space required for installation. The larger battery bank and solar array drives CAPEX cost high. The large battery bank drives down the system reliability. The weather creates unknown periods of energy generation from the solar and wind. Without the incorporation of a DC generator there will be long periods where the batteries remain in the low state of charge and this shortens the life of the battery, diminishes system reliability, and increases the OPEX cost.
The 80/20 RuleProducing 80% of the sites energy requirement using fuel and 20% using renewable energy is an optimal configuration. For typical lead acid battery technology, the last 20% charge requires low power over a long period of time. Powering the load and providing the finishing charge is an ideal application for the solar array. This allows the DC generator to work at it’s peak efficiency, when it’s providing the bulk charge into the battery and powering the load at the same time. The 20/80 RuleIf there is sufficient CAPEX budget and installation area at the site, using 80% renewable energy and 20% fuel is also an optimal configuration. In most regions of the world, trying to derive 100% of the site energy from renewable energy during the winter months or monsoon season can require the solar array and the battery bank to increase in size by a factor of two or three times. Allowing the DC generator to provide most of the energy during poor weather conditions greatly reduces the CAPEX cost and provides system backup in case of solar or battery failure. Because of variable weather conditions the CAPEX and OPEX costs favor the use of the DC generator. Power Diagram for a Solar Hybrid System (Summertime)
The graph shows the battery providing 2 discharge cycles per 24 hours and receiving one finishing charge and one bulk charge. A lead acid battery bank would be sized for a depth of discharge not to exceed 20%; the lower depth of discharge provides a greater number of charge cycles and this helps offset the penalty of 2 daily cycles. A wind generator can be added to the solar hybrid system to reduce fuel consumption and battery cycling. We recommend using a small wind generator to determine the available wind energy on-site and to produce usable power. The other choice is to install wind energy measuring equipment on-site, but the cost of instrumentation and a small wind generator or similar. After 1 or 2 years a year a determination can be made to remove the wind generator, increase its size, or leave it alone. Various Approaches to Powering Cell SitesPolar DC Cycling for both Off-Grid and On-Grid ApplicationsSame principal of operation as the Hybrid solution but without incorporating renewable energy. Field trials have shown a 70% and greater fuel savings over the conventional AC generators. Also reliability is enhanced and maintenance is reduced using the Polar Cycling solution.
The power output of a DC generator can be regulated so we can operate closer to the ideal engine power curve. This saves fuel because we can make use of smaller engines displacements. In the chart we show the DC generator operating at 80% of its rated power. Sizing an AC generator requires that it is larger in capacity than the sum of all the loads that may operate at the same time. Typically the sizing of the DC generator into an application is based on the amount of energy required in a 24 hour period plus charging losses in the battery divided by the desired generator runtime within the same period. AC CyclingAC generators can be used with rectifiers / battery chargers and operated in a cycle charging fashion; this also offers a fuel saving advantage over operating an AC generator 24 / 7.
The DC cycling is 25% to 40% more fuel efficient than the AC cycling solution. AC Generator operating 24/7Competition between telecommunications companies and the goal of making telephone and broadband services available to lower income groups is driving the need to reduce OPEX cost. Reducing energy costs presents the largest opportunity in reducing the cost to deliver service to customers! Running an AC generator 24 hours a day and seven days a week is the traditional but least efficient method of powering a cell site. The two principal problems of a constant run AC generator are the large engine displacement and operating while the loads are small. Typically 20 to 40 kW AC generators are used at sites where a 3 kW to 15 kW DC generator performs well. Larger AC generators are used because they have proven to last longer than smaller AC generators:
AC vs DC GeneratorField trials have shown 70% and greater fuel reduction over the conventional AC generators. Polar Power’s DC generator makes use of smaller displacement engines operating near their most fuel-efficient points. You can efficiently operate the Polar Power DC generator at 100% of its power rating. In comparison, the AC generator in the typical installation is operating a larger engine at less than 50% of its power rating. In the graph above the dotted red line representing the AC generator is consuming more fuel than the blue line for the DC generator. The AC generator running while the load is at a minimum power level represents the most significant waste of fuel. Using the DC cycling approach the DC generator is off and the load is powered by the battery. Polar DC generators offer a lower OPEX cost than AC generators
Polar’s DC generator systems are more reliable than the AC systems
If you want to improve reliability add a DC Generator rather than increase the Battery Bank.When optimizing a power system for efficiency and reliability too many engineers fail to create a balance between Power Generation and Energy Storage. Too frequently the battery, which is a storage device, gets placed in the role of a power generation device; compromising the efficiency and reliability of the system. For instance, in computer UPS systems, increasing the battery bank size is a solution to provide reliable power in the events of longer utility power outages. Increasing the battery bank size also compensates for problems of bad cells within the battery bank. In traditional Telecommunications Systems, BTS site batteries are used to back up the grid and follow the same example in computer UPS systems. Battery banks are increased in capacity to provide power for power outages of longer duration, to compensate for problems within the battery bank itself, or to allow sufficient time for service personnel to arrive at site with a generator. In Solar Photovoltaic Systems the battery stores the surplus energy produced by the solar and the stored energy powers the load at night and during poor weather conditions. Battery banks are increased in size to match the worst-case weather conditions, and to compensate for problems within the battery bank itself. The typical design principle on solar systems is to size the battery bank for 5 days of autonomy. It should be appreciated that increasing battery bank sizes to provide sole energy storage is very expensive and decreases reliability. Design engineers are now appreciating that, Diesel, LPG, or CNG can reduce the need for larger battery banks. Fuel is also an energy storage medium and together with a smaller battery bank will create a more efficient, reliable, and cost-effective system. Adding a DC Generator to the system is the most efficient and reliable means to improve system efficiency and reliability while reducing both the capital cost and operating costs of the system. The DC generator allows a system integrator the ability to reduce the size, maintenance, and cost of the power system. The DC Generator/Battery Bank System Application Example
Increasing the size of the battery bank does not help to increase reliability as the battery is only a storage device not a power producing device. The solution for increased reliability is at the power producing / energy conversion sources and not at the storage medium. Increasing reliability means improving the availability of power; therefore, to improve site reliability means adding a second DC generator and possibly more solar. Improving storage reliability requires the proper selection of battery chemistry and construction. Many applications have been using batteries that were optimized for standby applications and not cycling applications. And some battery manufacturers have exaggerated the performance of their batteries and cycling applications. Having an oversized battery bank on site simply means that you buy more time for the technician to arrive on site. And in rural areas it may take a week to get the technician on site. Once the technician is on site he is faced servicing a large dead battery. Solution is to keep the battery small and to make the power generation sources redundant. Backup Power and Prime Power GeneratorsThere are two classes of DC generators on the market, backup power and prime power. Backup power generatorsBackup power generators use light duty engines with common AC alternators rewound for lower voltages. The alternators typically do not use permanent magnets and instead use a wound rotating rotor with brushes and slip rings or an exciter. On the output of these generators is a large transformer / choke with huge electrolytic capacitors required to filter the power output to meet the low ripple requirements of Telcom power. These sets are built as cheaply as possible to compete with the lower cost AC generators. Engines are from the “lawn and garden” applications which are typically air cooled and have very small lubricating oil reservoirs. These light duty air cooled engines have a design life of between 500 to 1,000 hours of run time. Most small air cooled gas and diesel engines require between 8 to 30 hour oil maintenance intervals; this is attributed to the high oil temperatures of 160° C plus an under 1.6 liter oil capacity. There is water / fluid cooled “lawn and garden” type engines for the larger generator sizes and these engines improve upon the oil maintenance period, but durability is compromised due to the low cost light duty bearings supporting the crankshaft and pistons. The fluid cooled engines have a design life of 2,000 to 4,000 hours. What compromises the life of the small fluid cooled diesels is that the engines are run fast at speeds of around 3,600 RPM to save alternator and engine costs. Solar Hybrid systems engineers refer to the generator in their system as backup, they assume that either all generators are similar in performance or the generator will run less than a few hundred hours each year. We see project managers complaining about having to replace a light duty DC or AC generator 1 to 3 times a year. The high maintenance requirements of the light duty generators cannot meet required reliability so the system fails often.
Prime Power GeneratorsPrime power DC generators will incorporate permanent magnet alternators for increased efficiency and simplicity. DC alternators will incorporate 12 to 32 pole configurations with 3 to 6 phases. This eliminates the requirement for chokes and huge filter capacitors and provides for better efficiencies. Prime power generators use heavy duty, fluid cooled engines, with oil capacities of 2 to 17 liters with very heavy duty bearings. These generators operated at slower engine speeds of 1,500 to 2,600 RPM. Engine operation life will range from 16,000 to 35,000 run time hours. Electronics for backup generators tend to have limited communications and remote control features. Standard alarms are typically limited to: generator run, warning, and fail. To save production costs electronics are typically open to the environment, terminal strips are used in place of sealed connectors, and lower quality wire for connections. Polar builds its controls to automotive and military standards. We avoid terminal strips whenever possible, use gold plated sealed connectors, sealed electronics assemblies, plated copper wire with higher temperature and more chemical resistant insulation. Circuit isolation and lightning surge resistance are incorporated to our control design. To reduce the costs of site visits our DC generators can be monitored, controlled, and calibrated remotely. Given the loss of revenues due to a site being offline and the cost to get a qualified service technician on site, cutting cost on a generator does not make sense.
Traditional and New Ideas behind Sizing the Battery Bank CapacityOld: Solar and Wind systems, without a fuel sourced generator, have a design preference for 5 days of autonomy.
Old: Telecom sites that are powered by a reliable utility grid use a battery backup sized to power the load during average power outages. The more critical sites will incorporate larger battery banks for worst-case power outages. Here the battery banks are relatively small and there is limited need for backup generator due to grid reliability.
Old: Telecom sites that are powered by a less reliable utility grid that experiences longer and more frequent outages will incorporate a backup generator with the battery bank. The purpose of the battery bank is to power the load while the generator is starting or to continue powering the load should the generator fail to start. Battery banks are frequently sized with sufficient storage capacity to allow a service technician time to arrive on site to service the generator. 2 to 4 days of autonomy is commonly chosen and this presents a high CAPEX and OPEX cost.
Old: Telecom sites that are off grid and use an AC generator operating 24 / 7 use a battery bank that is sized with sufficient capacity to keep the site on line in the event one or more of the AC generators fail allowing time for the technician to affect repair.
Old: To improve the operational reliability of the generator by increasing the size of the battery bank to reduce the runtime and cycling of the generator. Telecom sites that are off grid and use either an AC generator or DC generator in conjunction with battery cycling to save fuel and reduce generator maintenance. These sites may also incorporate solar and wind to further reduce fuel consumption.
Continuous Run versus Cycling with BatteryContinuous If the load operates 24/7 at the same power level with only minimal fluctuations, a Polar DC generator can be tuned to meet this specific power requirement. For example if the load is 1500 W we can supply a DC generator to deliver 1500 W operating at an ideal engine RPM range. This type of configuration would limit the requirement for the battery bank and the system would not see the charging and discharging losses. Running 24 hours a day the DC generator will require a new or rebuilt engine every 1 to 2 years for diesel and 3 1/2 to 4 1/2 years for LPG (the alternator and controls are reused). Traditionally an AC generator is run 24/7 and on sizes less than 10 kW generators the generator may require replacement every 4 to 6 months. 20 kW sets are used on loads as small as 1.5 kW to increase operational life at the sacrifice of fuel efficiency. Cycling For the same application powering constant 1500 W load we would select an 8 kW DC generator and operate it approximately 5 hours a day. In this scenario a new or rebuilt engine for the generator would be required every 4.5 to 7 years or diesel and in 16 years for LPG. Discussion
Lithium Ion or Lead Acid BatteriesPolar has worked with Lithium Ion batteries over the past 3 years in various applications not pertaining to telecomm. Just recently we started incorporating Lithium Ion into our telecom installations with very good results. The Lithium Ion batteries have the following advantages over lead acid (flooded, AGM / Starved Electrolyte, Gel, etc.) in cycling applications:
Hydrogen Fuel CellsHydrogen Fuel cells are a promising future technology in an application to backup the utility grid at sites where disruption of power is very rare. The concept is not to install a backup battery and generator on site and instead use a fuel cell to convert the compressed hydrogen gas into electricity. The fuel cell combines oxygen from the ambient air with the hydrogen fuel and produce electricity and water; a very clean process. For all but the smallest power loads (i.e. 100 watt) the cost of the fuel cell is too expensive to be competitive with batteries and DC generator. If the goal is clean energy the DC generator can be tuned to run on hydrogen as a fuel at a lower cost than using a fuel cell. For sites that are off grid or serviced with utility power with frequent interruptions, hydrogen fuel is too expensive of a fuel. A convenient distribution of Hydrogen as a competitive fuel source is decades away into the future. Compressed natural gas and LPG are significantly lower in cost and more readily available now. Natural gas and LPG have advantages over diesel:
Difficulties in Implementation of Improved Power SystemsThere is confusion over the role of batteries within power system that operate off grid or are serviced with intermittent utility power. Battery stores energy that is supplied by other sources including: utility power, solar, wind, and generators. Batteries provide transitional or a load leveling source of power. Batteries are limited in the amount of energy in which they can cost-effectively store. Increasing the battery banks size does not increase the reliability of backing up the utility grid or generator. To back up the generator use a second generator. To backup the utility you add a generator. To increase the site’s autonomy you increase the amount of fuel or solar on site. If a larger battery bank is used to allow time for the technician to effect repair the site may still go down if the technician is unable to repair on the first visit. The solution is to have the technician travel with the spare generator or it is more cost-effective to reduce the battery bank size and use those funds to install a second generator on site. Now the site’s reliability is not dependent on the arrival time of the technician or any additional cost incurred to expedite the technician’s arrival on site. The space available at most sites is very limited, many program managers feel there is no room for more than one AC generator and the battery bank presents itself as a more compact “solution”. This is not true for the Polar DC generator; our DC generators are significantly smaller in size than the AC generator or the additional batteries. Telecom companies competitively bid the generator requirement and seek the lowest bidder and then spend a far greater amount of capital on the battery bank. If they spent more capital on a reliable generator they would be able to save significantly on the CAPEX and OPEX costs by purchasing smaller battery banks. With so many advantages including the large fuel savings why are there so few DC generators installed in telecomm sites? To discover what are the factors making a more reliable generator please continue exploring the Polar Power website
With non-disclosure agreements in place, Polar has limitations on disseminating field performance results from one Telcomm company to another. With limited field trial data and experience within the Telcomm, each Telcomm wants to validate the technology using their own sites. Most field trials last 1 to 3 years. Unfortunately by the time the field trials are completed frequently the Telcomm employees that managed the trials change jobs or departments and their knowledge is not transferred within the company. A program manager will typically compare the cost of an AC generator against the cost of the DC generator system. The AC generator is typically priced without: automatic start stop controls, remote monitoring electronics and software, transfer switch, and the battery charger/rectifier. The Polar DC generator system does not require the transfer switch, battery charger/rectifier, and includes the electronics and software for remote monitoring and fully Automatic operation. AC generators enjoy wide distribution with high inventory levels providing most programs with short delivery timeframes. DC generators are manufactured to order and do not presently benefit from distributors stocking; this will change when the Telcomm’s start purchasing in volume. Frequently trials ending with very favorable results for the DC generator still encounter Telcomms purchasing the AC generators because of the shorter delivery schedules. The field trial itself sets the program schedule behind forcing the purchase of AC generators. If there is enough schedule time for the Telcomms to purchase a DC generator sets frequently they go out for bid and purchase lower-cost DC generators that fail meet their requirements. Not all DC generators are created equal. Unreasonable ExpectationFor an on grid BTS site that requires high reliability the utility grid is backed up with a generator and An unreasonable expectation is having a prime power site (without grid power) using one generator If the off grid site requires a higher degree of reliability then the site requires multiple sources Final WordAccording to latest figures issued by the GSM Association, around 640,000 off-grid base stations (BTS) will be rolled out across emerging markets by 2012. The target is for 118,000 of these BTSs to be powered by renewable energy. It is clear that rising fuel prices and environmental considerations such as emission control, noise, carbon footprint and environmental impact are all issues that will be influencing specification decisions. With rapidly rising fuel costs, de-regulation and elimination of subsidies for fuel in many developing economies around the world, DC Hybrid solutions will provide the ideal solution by:
|
|
|||